Communication
8.4 Ethernet
8.4.4.2
Configuring or changing an IP address for a CPU or device in your project
You must enter the following IP information for each S7-200 SMART CPU that is attached to
your Ethernet network:
Note
The CPU models CPU CR20s, CPU CR30s, CPU CR40s, and CPU CR60s have no
Ethernet port and do not support any functions related to the use of Ethernet
communications.
● IP address: Each CPU or device must have an Internet Protocol (IP) address. The CPU
or device uses this address to deliver data on a more complex, routed network. Each IP
address is divided into four 8-bit segments and is expressed in a dotted, decimal format
(for example, 211.154.184.16). The first part of the IP address is used for the Network ID
(What network are you on?), and the second part of the address is for the Host ID
(unique for each device on the network). An IP address of 192.168.x.y is a standard
designation recognized as part of a private network that is not routed on the Internet.
Note
All S7-200 SMART CPUs have a default IP address of: 192.168.2.1
Note
You must have a unique IP address for each device on your network.
404
System Manual, V2.3, 07/2017, A5E03822230-AF
S7-200 SMART