Wireless temperature and universal i/o transmitters (106 pages)
Summary of Contents for Honeywell ST 800 Series
Page 1
ST 800 Series HART/DE Option User’s Manual 34-ST-25-38 Revision 5.0 July, 2014 Honeywell Process Solutions...
Page 2
In no event is Honeywell liable to anyone for any indirect, special, or consequential damages. The information and specifications in this document are subject to change without notice.
About This Manual This manual provides the details of programming Honeywell ST 800 SmartLine Pressure Transmitters for applications involving HART versions 5, 6, and 7 and Honeywell’s Digitally Enhanced (DE) communication protocols. For installation, wiring, and maintenance information refer to the ST 800 SmartLine Pressure Transmitter User Manual, document number 34-ST-25-35.
Page 4
Patent Notice The Honeywell ST 800 SmartLine Pressure Transmitter family is covered by one or more of the following U. S. Patents: 5,485,753; 5,811,690; 6,041,659; 6,055,633; 7,786,878; 8,073,098; and other patents pending. Support and Contact Information For Europe, Asia Pacific, North and South America contact details, see back page or refer to the...
1 ST 800 Physical and Functional Characteristics 1.1 Overview This section is an introduction to the physical and functional characteristics of Honeywell’s family of ST 800 SmartLine Pressure Transmitters. 1.2 Features and Options The ST 800 SmartLine Pressure Transmitter is available in a variety of models for measuring Differential Pressure (DP), Gauge Pressure (GP), and Absolute Pressure (AP).
Refer to the ST 800 SmartLine User’s Manual, document number 34-ST-25-35 for installation and wiring details. Figure 1 – ST 800 Major Assemblies Figure 2 – Electronics Housing Components Page 2 ST 800 Series HART/DE Option User’s Manual Revision 5.0...
Honeywell Multi-Communication (MC) Toolkit (not supplied with the Transmitter) can facilitate setup and adjustment procedures. Certain adjustments can be made through an Experion Station or a Universal Station if the Transmitter is digitally integrated with Honeywell’s Experion or TPS/TDC 3000 control system.
• With a display – Complete Transmitter configuration is possible for HART & DE devices. You can also use the Honeywell MCT202 Configuration Tool to make any adjustments to an ST 800 Transmitter. The MCT202 tool has two applications; MC Toolkit and FDC. Using the MC Toolkit application you can adjust the ST 800 DE model configuration.
A comprehensive on screen menu guides the way o Configure the transmitter o Configure the display o Set zero and span • Zero and span settings without optional display Revision 5.0 ST 800 Series HART/DE Option User’s Manual Page 5...
Figure 4 – DE Mode Value Scaling As indicated at the right of Figure 4, output values of process variables, as well as communications are transferred to a receiving device digitally. The digital coding is Honeywell proprietary, which requires the use of DE-capable Honeywell control equipment.
HART communication will not bump process variables. In multi-drop mode, up to 16 transmitters in HART 5 (addresses 0-15) and up to 64 transmitters in HART6/7 (addresses 0-63) can exist on the two-conductor network. Revision 5.0 ST 800 Series HART/DE Option User’s Manual Page 7...
Honeywell MC Toolkit or MCT202. The name MC Toolkit or Toolkit and MCT202 are used interchangeably as MCT202 is the model name for the Honeywell MC Toolkit product. Furthermore,...
MC Toolkit–Transmitter Electrical/Signal Connections Figure 6 displays how to connect the MC Toolkit directly to the terminals of a HART or DE Transmitter (top), and a HART-only Transmitter (bottom). Revision 5.0 ST 800 Series HART/DE Option User’s Manual Page 9...
4 DE Transmitter Configuration 4.1 Configuration Personnel Requirements The configuration processes in this section reflect the assumption that you will use the Honeywell MC Toolkit Configuration Tool to configure an ST 800 SmartLine Pressure Transmitter. The MC Toolkit application is used to configure Honeywell ST 3000 Pressure Transmitter, STT 3000 Smart Temperature Transmitters, as well as the ST 800 SmartLine Pressure Transmitter.
4. When the warning message for connecting to a DE device appears, select OK. 5. Process the three warning pop-ups as appropriate, and then select OK in the Put loop in Manual… pop-up. The QUICK MONITOR box will be displayed. Page 12 ST 800 Series HART/DE Option User’s Manual Revision 5.0...
Page 21
Output Mode during calibration, and was not subsequently cleared. If you confirm the message (Yes answer), the display will exit the DE MAIN MENU. Revision 5.0 ST 800 Series HART/DE Option User’s Manual Page 13...
Manufacturer’s firmware version identifier PROM ID Number PROM ID Number Scratch Pad Up to 32 alphanumeric characters Select the Back button to go back to the DE MAIN MENU. Page 14 ST 800 Series HART/DE Option User’s Manual Revision 5.0...
See the ST 800 FS Direction SmartLine Transmitter User Manual for details. Select the Back button to go back to the DE MAIN MENU. Revision 5.0 ST 800 Series HART/DE Option User’s Manual Page 15...
You can use the following formula to find the turndown ratio using the range information for your Turndown Ration = (Upper Range Value − Lower Range Value) Transmitter. Note that ST 800 Transmitters are specified with a minimum of 100:1 turndown capability. Page 16 ST 800 Series HART/DE Option User’s Manual Revision 5.0...
As shown in Figure 7, the dropout point is between 0.4% and 0.5% of differential pressure, depending on direction Figure 7 – Differential Pressure Square Root Conformity Curve Revision 5.0 ST 800 Series HART/DE Option User’s Manual Page 17...
4.3.2 Floating point (for square root configurations) Flow EU Lower Value Floating point (for square root configurations) Select the Back button to go back to the DE MAIN MENU. Page 18 ST 800 Series HART/DE Option User’s Manual Revision 5.0...
Device Status button to display device status. Communication Refer to the “Messages and Diagnostic Codes” section Status of the MCT202 Toolkit manual. Select the Back button to go back to the DE MAIN MENU. Revision 5.0 ST 800 Series HART/DE Option User’s Manual Page 19...
New1. e. After entering the file name, select the Save button to display the DE MAIN MENU. Page 20 ST 800 Series HART/DE Option User’s Manual Revision 5.0...
• Parameter Set 1 consists of the description of Transmitter according to bus type, device type, serial and model number, and the manufacturer. Revision 5.0 ST 800 Series HART/DE Option User’s Manual Page 21...
Parameter Set 2 permits entering/editing the values for the LRL, URL, LRV, URV, PV Units, Damping, SV Units, Line Filter frequency, Sensor Type, and the Conformity selection. • Parameter Set 3 is oriented primarily to the Honeywell SmartLine Temperature Transmitter models for monitoring purposes. Save to a File Saving to a file in offline mode will let you add an edited configuration to a working file.
The other HART configuration Tools are Honeywell Experion in conjunction with FDM, iDTMs running on FDM or Pactware, and Emerson 375/475. The organization of Device Configuration and Parameter Descriptions on page 33 is given in Table 11.
Tap to navigate to Offline configuration screen. Tap to navigate to Manage DDs screen. Tap to navigate to Settings screen. Tap to select the highlighted menu option. Tap to quit FDC. Page 24 ST 800 Series HART/DE Option User’s Manual Revision 5.0...
With this option enabled, FDC creates necessary log files for troubleshooting and diagnostics. These files are stored in SD Card\FDC folder. Note: You must not enable this option unless suggested by Honeywell TAC because this may impact the application performance.
If the DD file already exists, then the following message appears. Tap Yes to overwrite the existing DD files. If the DD file is added successfully, a success message appears. Page 26 ST 800 Series HART/DE Option User’s Manual Revision 5.0...
HART device with live communication. After making changes to the device you can also save a snapshot of the device data as history to later transfer it to FDM for record and audit purposes. Revision 5.0 ST 800 Series HART/DE Option User’s Manual Page 27...
The workspace area on the device homepage consists of 4 tabs on the left hand side. Selecting a tab displays functions/information associated with that tab on the right hand side. Page 28 ST 800 Series HART/DE Option User’s Manual Revision 5.0...
FDC across all devices. For the sake of explanations, the right side options under this tab shall be referred as “Entry points” throughout the rest of the document. Revision 5.0 ST 800 Series HART/DE Option User’s Manual Page 29...
Page 38
Currently the only option it provides is called as Save History. Using this option you can save the snapshot of the device variables. This snapshot is saved in a format which can be later imported as a history record in FDM. Page 30 ST 800 Series HART/DE Option User’s Manual Revision 5.0...
“Device Configuration” pages in this document. However it must be noted that this does not prohibit you from performing other device operations as explained above. Revision 5.0 ST 800 Series HART/DE Option User’s Manual Page 31...
Page 40
Alternately you can access the full EDDL features by selecting the “My Device” Tab Navigate through the Menus to access various functions. See Table 11for lists all the parameters in the ST 800. Page 32 ST 800 Series HART/DE Option User’s Manual Revision 5.0...
Displays the Lower Transducer Limit of the transmitter in user selected engineering units. Online/ PV UTL Displays the Upper Transducer Limit of the transmitter in user selected engineering units. Revision 5.0 ST 800 Series HART/DE Option User’s Manual Page 33...
Page 42
Enter a long tag name up to 32 alphanumeric characters. Cfg chng count Configuration Change Counter – this counter keeps track of the number of times any configuration parameter has been changed Page 34 ST 800 Series HART/DE Option User’s Manual Revision 5.0...
Page 43
PV Source status of the corresponding AI channel is changed to AUTO / SUB or the transmitter is power cycled. For more information, refer to the Experion Knowledge Builder Revision 5.0 ST 800 Series HART/DE Option User’s Manual Page 35...
Page 44
Write Protect is “Enabled” if either the write protect jumper on the electronics board is in the “ON” position or the firmware write protect has been enabled. Page 36 ST 800 Series HART/DE Option User’s Manual Revision 5.0...
Page 45
Displays the time and date history records for the last three Zero Trim calibrations. Reset Correct Records Displays the time and date history records for the last three times Reset Corrects was issued. Revision 5.0 ST 800 Series HART/DE Option User’s Manual Page 37...
Page 46
Displays all possible Extended Device Status faults and indicates OFF for inactive faults or ON for active faults. Additional Status Displays an advanced diagnostic detailed breakdown of all Critical and Non-Critical faults Page 38 ST 800 Series HART/DE Option User’s Manual Revision 5.0...
Page 47
- If the reconfigured value is greater than tamper attempts, then the tamper attempts value is retained. If the reconfigured value is smaller than tamper attempts, then the tamper attempts value is clamped to the reconfigured attempts. Revision 5.0 ST 800 Series HART/DE Option User’s Manual Page 39...
Page 48
Master Reset of the device. If “Yes” is selected to unlock the device, the lock state will be cleared. Page 40 ST 800 Series HART/DE Option User’s Manual Revision 5.0...
Page 49
Linear (output scaled linearly per configured range) Square Root (output scaled as square root conversion per configured range - for flow measurements) PV % range: Displays the current value of AO (analog output) in % Revision 5.0 ST 800 Series HART/DE Option User’s Manual Page 41...
Page 50
Note that this function is only available when “Loop mA” (Loop Current mode) is Enabled. D/A trim: perform an analog output calibration at 4.00 and 20.00 mA (0% and 100% output). Page 42 ST 800 Series HART/DE Option User’s Manual Revision 5.0...
Page 51
*This parameter can be changed when PILD is disabled. When PILD is enabled user can still change the parameter if PILD is in Monitoring mode and not in Training mode Revision 5.0 ST 800 Series HART/DE Option User’s Manual Page 43...
Page 52
Select from 3 to 30 seconds. Contrast Level: Select a display contrast level from 1(low) to 9 (high) or choose the “default” (5). Page 44 ST 800 Series HART/DE Option User’s Manual Revision 5.0...
Page 53
License Key used to enable specific feature or function Displays the current values for all of the pertinent operating Online/Device parameters listed in this table, plus revision information. Setup/Review Parameters are not configurable in this menu. Revision 5.0 ST 800 Series HART/DE Option User’s Manual Page 45...
Reporting Status Posted? Change Allowed? Jumper missing Jumper missing Jumper missing Jumper missing The sections below give some examples as to how to edit the configuration parameters and execute Methods. Page 46 ST 800 Series HART/DE Option User’s Manual Revision 5.0...
6. Click Send. The Send to Device screen will be displayed. 7. Select the PV Unit check box. 8. Click Send to download the change to the Transmitter or Return to continue making changes. Revision 5.0 ST 800 Series HART/DE Option User’s Manual Page 47...
LRV first . You can also use the local zero and span adjustments on the Transmitter to set the LRV and URV values. 1. Starting at the My Device menu, make the following menu selections: Shortcuts > Device setup > Calibration > Calibration Methods > Apply values. Page 48 ST 800 Series HART/DE Option User’s Manual Revision 5.0...
To save device history, perform the following steps. On Device Home page, tap Tools. Select Save History and tap Select The Save History page appears. Revision 5.0 ST 800 Series HART/DE Option User’s Manual Page 49...
All operations allowed on Device History Record in FDM will be allowed for the record imported through the MC Toolkit handheld. Note: For more details on using FDM Import/Export feature, refer to section Importing and Exporting Device History in FDM User’s Guide. Page 50 ST 800 Series HART/DE Option User’s Manual Revision 5.0...
Tap Option>Save to persist the change Tap Return to return to My Views page. You would see two options with the names you gave to the newly created views. Revision 5.0 ST 800 Series HART/DE Option User’s Manual Page 51...
Page 60
Edit the parameters that are Read / Write and select Send. For more details on any of the FDC features, refer the “MC Tookit User Manual, document # 34-ST- 25-20.” Page 52 ST 800 Series HART/DE Option User’s Manual Revision 5.0...
Note: In case if the offline configuration template is already imported, an overwrite message appears. 11. Tap OK to return to the Offline Configurations page. The device details appear on the bottom of the page. Revision 5.0 ST 800 Series HART/DE Option User’s Manual Page 53...
Page 62
The Offline – Review and Send page appears with the list of selected variables. 22. Tap Send and the process to send the variables to the device starts. Once the downloading is complete, the following page appears. Page 54 ST 800 Series HART/DE Option User’s Manual Revision 5.0...
Page 63
Note: If the variables are downloaded successfully, status appears as SUCCESS in green color; and if failed, status appears as FAILED in red color. 23. Tap Finish to return to FDC Homepage. Revision 5.0 ST 800 Series HART/DE Option User’s Manual Page 55...
6.2 Calibration Recommendations If the Transmitter is digitally integrated with a Honeywell Total Plant Solution (TPS) system, you can initiate range calibration and associated reset functions through displays at the Universal Station, Global User Station (GUS), and Allen-Bradley Programmable Logic Controllers (PLCs). However, a range calibration using the MC Toolkit with the Transmitter removed from service is recommended.
5. Select the desired constant-level Output: 0 %, 100 %, or Other (any of 0 % - 100 %). 6. Select the Set button. You will be prompted to confirm that you want to put the Transmitter in output mode. Revision 5.0 ST 800 Series HART/DE Option User’s Manual Page 57...
6.7 Input Calibration Procedures Description The input calibration process consists of the following three parts: • Correcting the input at zero pressure. • Correcting the input LRV. • Correcting the input URV. Page 58 ST 800 Series HART/DE Option User’s Manual Revision 5.0...
1. Start the MC Toolkit application. Establish communication between the Transmitter and the MC Toolkit. 2. From the DE MAIN MENU, select Configure to call up the DE CONFIGURE display. 3. From the DE CONFIGURE display: Revision 5.0 ST 800 Series HART/DE Option User’s Manual Page 59...
Page 68
DP transmitter). As indicated below, this procedure will shift the slope up or down to eliminate the error at the zero reference. The slope (angle) of the response is unchanged. Page 60 ST 800 Series HART/DE Option User’s Manual Revision 5.0...
3. Adjust the PV input pressure to the exact value of the LRV entered in the DE CONFIGURE display. 4. Select the OK button; this message appears: 5. Observe the input pressure at the applied value; when it is stable, select the OK button. Revision 5.0 ST 800 Series HART/DE Option User’s Manual Page 61...
2. Adjust the PV input pressure to the exact value of the URV entered in the DE CONFIGURE display. 3. Select the OK button. 4. When the transmitter has completed the URV correction, this message appears. 5. Select OK to acknowledge. Page 62 ST 800 Series HART/DE Option User’s Manual Revision 5.0...
Variable (PV) input range such that 4 mA corresponds to the LRV of 0% and 20 mA corresponds to the URV of 100%. Figure 13 shows the PV scale and representative process system connections. Figure 13 – DE Analog Mode Scaling and Test Connections Revision 5.0 ST 800 Series HART/DE Option User’s Manual Page 63...
Page 72
Step Size to 10 or 100. e. After establishing the zero current level (4 mA), select Set Output To 100%. A meter reading of 20 mA corresponds to 5 volts. Page 64 ST 800 Series HART/DE Option User’s Manual Revision 5.0...
1. Establish the test connections shown below. Then start the MC Toolkit application to display the DE MAIN MENU. Figure 14 – Setup to Manually Set the PV LRV and URV Revision 5.0 ST 800 Series HART/DE Option User’s Manual Page 65...
Page 74
(0 %) level, then select Set LRV. b. If the displayed value is satisfactory, select Yes to copy the Input Value to the LRV in the Transmitter. If not, select NO and repeat this step. Page 66 ST 800 Series HART/DE Option User’s Manual Revision 5.0...
Page 75
Call up the DE CONFIGURE display, and observe that the settings are established in Steps 4 and 5. b. This concludes the procedure to manually set the operating range. Revision 5.0 ST 800 Series HART/DE Option User’s Manual Page 67...
DE MAIN MENU is displayed, and establish communication with the Transmitter. 2. From the DE MAIN MENU, select Calibration. The CALIBRATION menu will be displayed. 3. Select Reset Corrects. The following prompt will be displayed. Page 68 ST 800 Series HART/DE Option User’s Manual Revision 5.0...
Page 77
("characterization") values. It is intended for use only when excessive corrections render the transmitter inaccurate. It is highly recommended that input calibration procedure be performed after calibration reset. Revision 5.0 ST 800 Series HART/DE Option User’s Manual Page 69...
Digital Voltmeter or millimeter with 0.02% accuracy or better • MC Toolkit Calibration standard pressure source with a 0.02% accuracy • 250 ohm resistor with 0.01% tolerance or better. Page 70 ST 800 Series HART/DE Option User’s Manual Revision 5.0...
Return back to the ”Enter Meter Value” prompt until the field device output equals the reference meter o Select Yes and press Enter 8. The prompt notifies you that the field device will be returned to its original output Revision 5.0 ST 800 Series HART/DE Option User’s Manual Page 71...
7. You will be prompted to remove the loop from automatic control. Press OK 8. When prompted, adjust the pressure source to apply pressure equal to the URV (100%), and press OK. 9. When pressure stabilizes, press OK. Page 72 ST 800 Series HART/DE Option User’s Manual Revision 5.0...
Run the Methods and follow the screen prompts to read the Calibration Records. Select “My Device\Device Setup\Calibration” to select the following calibration records • Correct URV Records • Correct LRV Records • Zero Trim Records • Reset Corrects Records Revision 5.0 ST 800 Series HART/DE Option User’s Manual Page 73...
Last Corrects Rec Date and Time of last Reset corrects done displayed in mm/dd/yyyy format Prev Corrects Rec2 Date and Time of current Reset corrects done displayed in mm/dd/yyyy format Page 74 ST 800 Series HART/DE Option User’s Manual Revision 5.0...
:-> Cal B LRV :-> Cal C URV :-> Cal C LRV :-> Calibration Selection: A or B or C, AUTO Select : ->Active Calibration: Cal A, Cal B, Cal C Revision 5.0 ST 800 Series HART/DE Option User’s Manual Page 75...
Set-up User enters a date once during device lifetime. Once date is entered no further updates are possible and value becomes read only and is permanently saved. Page 76 ST 800 Series HART/DE Option User’s Manual Revision 5.0...
PV passed above “PV Upper Stress Limit” (in days, hours and minutes). Set-up None – initialized to zero prior to leaving the factory. Backup once each 8 hour period Revision 5.0 ST 800 Series HART/DE Option User’s Manual Page 77...
“PV Lower Stress Limit” (in days, hours and minutes). Set-up None – initialized to zero prior to leaving the factory. Backup once each 8 hour period Page 78 ST 800 Series HART/DE Option User’s Manual Revision 5.0...
Last SV device’s Meterbody Temperature has Down passed below the value of “SV Lower Stress Limit” (in days, hours, and minutes). Set-up None. Backup once each 8 hour period Revision 5.0 ST 800 Series HART/DE Option User’s Manual Page 79...
Description Accumulation of minutes that device’s Upper Stress Electronics Temperature has been above Limit the value of “ET Upper Stress Limit”. Set-up None. Backup once each 8 hour period Page 80 ST 800 Series HART/DE Option User’s Manual Revision 5.0...
Last ET Down device’s Electronics Temperature has passed below the value of “ET Lower Stress Limit” (in days, hours, and minutes). Set-up None. Backup once each 8 hour period Revision 5.0 ST 800 Series HART/DE Option User’s Manual Page 81...
“Time Since Last Event” to be Parameters reset to zero. Within a short period of time “Min Op Voltage” will assume operating voltage value. Set-up User actuates as desired. Page 82 ST 800 Series HART/DE Option User’s Manual Revision 5.0...
Sensor CPU Temperature has Temp. Down passed below the value of “Min Sensor CPU Temp” (in days, hours and minutes). Set-up none Backup once each 8 hour period Revision 5.0 ST 800 Series HART/DE Option User’s Manual Page 83...
Possible values are 0.0 to 1.00 to the second decimal places. Current Mode Current Work Mode If PILD is enabled, modes are: • Training • Monitoring If PILD is disabled, no output. Page 84 ST 800 Series HART/DE Option User’s Manual Revision 5.0...
Page 93
Tooltips. It is a known FDM limitation and future FDM releases will address this issue. Value of 1.293723E-06 shows up as 0 in the Edit field Revision 5.0 ST 800 Series HART/DE Option User’s Manual Page 85...
Page 94
AP and blocked. operation. GP Transmitter only when PILD is Noise in process is PILD is not applicable to this specific enabled) too low. situation. It’s suggested to disable PILD. Page 86 ST 800 Series HART/DE Option User’s Manual Revision 5.0...
No DAC Calibration Tamper Alarm Meter Body Unreliable Comm Loop Current Noise AO Out of Range URV Set Err. Span Config Button LRV Set Err. Zero Config Button PILD Blockage Detected Revision 5.0 ST 800 Series HART/DE Option User’s Manual Page 87...
DAC compensation. No Factory Possible causes: Calibration Factory Calibration is missing. Accuracy will be compromised. Resolution: Replace the Meter Body or return the device for Factory Calibration. Page 88 ST 800 Series HART/DE Option User’s Manual Revision 5.0...
Page 97
The Display has been disconnected or configuration data has been corrupted. Resolution: Secure Display connections and recheck. If problem persists, reset the device. If the problem still persists, replace the Display Revision 5.0 ST 800 Series HART/DE Option User’s Manual Page 89...
Page 98
Calculated Analog output is either above or below the specified Loop Current Limits. The transmitter input is not in specified range. Resolution: Check the transmitter input and verify the configured operating range. Page 90 ST 800 Series HART/DE Option User’s Manual Revision 5.0...
Page 99
PILD when the process and transmitter is in normal operation. For case 3, PILD is not applicable to this specific situation. It’s suggested to disable PILD. Revision 5.0 ST 800 Series HART/DE Option User’s Manual Page 91...
Possible causes: fault or bad checksum Sensor characterization is corrupt or there is a Sensor firmware failure Resolution: Reset the device. If the problem persists, replace the Meter Body. Page 92 ST 800 Series HART/DE Option User’s Manual Revision 5.0...
Page 101
Replace Meter Body and recalibrate if needed. Current Fixed Possible causes: Output current is fixed and not varying with applied input. Output Mode is active. Resolution: Exit Output mode if active. Revision 5.0 ST 800 Series HART/DE Option User’s Manual Page 93...
Page 102
Meter Body temperature is too high. Accuracy and life span may decrease if it remains high. Resolution: Verify the environment temperature is within specification. Take steps to insulate Meter Body from temperature source. Page 94 ST 800 Series HART/DE Option User’s Manual Revision 5.0...
Feature requires license: PILD Field upgrade for ST 800 (Part Number - 50097038- 501) • The factory or Honeywell factory] generates and sends a License Key to customer. • The customer installs the license by selecting the “Enter License Key” method on the Device Setup->Upgrade Options menu.
Sensor Firmware: 1.03 Please reference your User Manual on how to obtain firmware revision numbers from a device. If you need technical support contact Honeywell GTS at 1-800-423-9883. • Place an order for the ST800 PILD Field Upgrade kit, part number 50097038-501. Include...
MC Toolkit FDC application. Refer to Table 11 for a complete listing of all the parameters and details. In the following sections, emphasis is given to show the various DTM screens. Revision 5.0 ST 800 Series HART/DE Option User’s Manual Page 97...
10.5 ST 800 Online Parameterization On selecting Parameter/Online Parameterization, the DTM home page is displayed as shown below. Page 98 ST 800 Series HART/DE Option User’s Manual Revision 5.0...
Basic Setup: • Provides Device Setup information (Tag, Device Type, MB Type etc.) Calibration: • Provides access to all the Calibration functions Refer to the Table 11 for more details Revision 5.0 ST 800 Series HART/DE Option User’s Manual Page 99...
Refer to Table 11 for more details Device Information Allows access to both read only parameters and read/write parameters. Provides access to Message, Clear Message and Maint Mode. Page 100 ST 800 Series HART/DE Option User’s Manual Revision 5.0...
Shows the Blow out Image of ST 800 System Setup: Shows the Image how to connect the Transmitter 10.7 Calibration Page The Calibration Page provides access to all of the calibration methods and records. Revision 5.0 ST 800 Series HART/DE Option User’s Manual Page 101...
Refer to the Calibration Records in for more details Reset Corrects Records • Prev Corrects Resets • Last Corrects Resets • Curr Corrects Resets Refer to the Calibration Records in for more details Page 102 ST 800 Series HART/DE Option User’s Manual Revision 5.0...
10.8 Process Variables Select to see the Trending Charts All the Process Variables are graphically represented in this screen. Select Trend Charts to see the Trending Charts Revision 5.0 ST 800 Series HART/DE Option User’s Manual Page 103...
10.10 Device Status Shows Critical and Non-Critical status and context-sensitive help when gliding the mouse over an individual status. Refer “Troubleshooting and Maintenance” for more details on individual status details Revision 5.0 ST 800 Series HART/DE Option User’s Manual Page 105...
Shows Help on Critical, Non-Critical when you click on “Help – Critical Diag” or “Help – Non-Critical Diag” buttons. Also, extended status can be seen by clicking the “Additional Status” button. Page 106 ST 800 Series HART/DE Option User’s Manual Revision 5.0...
• Power Up Diagnostics • PILD Status Access the relevant tab to read the Diagnostic parameters or run the Diagnostics Methods Refer ”HART Advanced Diagnostics” section for more details. Revision 5.0 ST 800 Series HART/DE Option User’s Manual Page 107...
10.13 Services This allows configuration of Tamper Alarm and Write Protect mode. Refer “Device Configuration and Parameter Descriptions” for more details. Configuration of Tamper Alarm Page 108 ST 800 Series HART/DE Option User’s Manual Revision 5.0...
10.14 Detailed Setup Shows Sensor Limits, Output Condition, Signal Condition and Burnout level selections. Refer Device Configuration and Parameter Descriptions for more details. Revision 5.0 ST 800 Series HART/DE Option User’s Manual Page 109...
10.15 Meterbody Selection Select the Meter Body Selections to see the Material of Construction details 10.16 Display Setup Allows configuring the Display from the Host. Page 110 ST 800 Series HART/DE Option User’s Manual Revision 5.0...
Refer “ST 800 SmartLine Pressure Transmitter User’s Manual: 34-ST-25-35 , Advanced Display Menu and Basic Display Menu sections” for more details. 10.20 Review Summary screen showing all the parameters. Revision 5.0 ST 800 Series HART/DE Option User’s Manual Page 111...
10.21 ST 800 Offline Parameterization On selecting Parameter/ Parameterization, the Offline parameter configuration page will be displayed. Select Device / Load to Device to download the Offline Configuration to the connected device. Page 112 ST 800 Series HART/DE Option User’s Manual Revision 5.0...
Experion R400 to R300 Experion below R300 FDM R430 FDM R410 – R302 FDM Below R302 Refer the respective Tools’ User Manual for details on loading the DD file on these Tools. Revision 5.0 ST 800 Series HART/DE Option User’s Manual Page 113...
Page 122
Page 114 ST 800 Series HART/DE Option User’s Manual Revision 5.0...
Measured differential pressure in Pascals in PV4 algorithm Absolute pressure of flowing gas Reduced pressure Static pressure at upstream point Process Manger Pounds per Square Inch PSIA Pounds per Square Inch Absolute Revision 5.0 ST 800 Series HART/DE Option User’s Manual Page 115...
Page 124
Upper Range Limit Upper Range Value Universal Station Volts Alternating Current Volts Direct Current HART Highway Addressable Remote Transmitter HART Communication Foundation EEPROM Electrically Erasable Programmable Read Only Memory Page 116 ST 800 Series HART/DE Option User’s Manual Revision 5.0...
Page 125
Offline Configuration ..........53 Series, Model and Number ........3 Online configuration ..........27 Transmitter Adjustments ........... 4 Overview of Device Homepage ........ 28 Procedure to Enter the Transmitter Tag ....See Revision 5.0 ST 800 Series HART/DE Option User’s Manual Page 117...
Page 126
Procedure to Install and Run the DTM ..... 97 Process Variables ........... 103 Screen Configuration ..........111 Services ..............108 ST 800 Offline Parameterization ......112 ST 800 Online Parameterization ......98 Trend Charts ............104 Page 118 ST 800 Series HART/DE Option User’s Manual Revision 5.0...
Page 127
Phone: (86-21) 5257-4568 Fax: (86-21) 6237-2826 Singapore Honeywell Pte Ltd. Phone: +(65) 6580 3278 Fax: +(65) 6445-3033 South Korea Honeywell Korea Co Ltd Phone: +(822) 799 6114 Fax: +(822) 792 9015 Revision 5.0 ST 800 Series HART/DE Option User’s Manual Page 119...
Page 128
For more information To learn more about SmartLine Transmitters, visit www.honeywellprocess.com Or contact your Honeywell Account Manager Process Solutions Honeywell 1250 W Sam Houston Pkwy S Houston, TX 77042 Honeywell Control Systems Ltd Honeywell House, Skimped Hill Lane Bracknell, England, RG12 1EB...