Parameters - Siemens SIPROTEC 7SS52 Operation Manual

Table of Contents

Advertisement

Common parameters
6000 CHANGE
SETTINGS
6100 SETTINGS:
BB–Diff.Protec ?
6101 STAB FAC:BZ =.65
6102 I>DIFF. :BZ =1.00
6103 STAB FAC:CZ =.50
6104 I>DIFF. :CZ =1.00
6105 NORM BAS IN =1000.0
6106 TRIP EXTEND =.10
6107 BI TRIPENAB =not existent
6108 T–CB
OPEN =0
6200 SETTINGS:
Bkr.Fail Protec?
6201 BF BI MODE
=1–chanelWithSup
6202 STAB FAC:BF =.50
6203 I>DIFF. :BF =2*I>BF (DA 6700)
6204 TIME UNB BF =.25
6205 T–BF IMPULS =.50
6206 T–CB FAULT
=.10
6207 TR REPOPMOD =single–phase
6208 T–TRIP
REP =.12
_______________
Ino – Normalized nominal current related to base current transformer
(current transformer with highest transformation ratio)
Nominal current of the base current trans-
former
DA 67XY with XY = bay number 01 to 48
?
(min.
1)
I/Ino
(min.
(min.
I/Ino
(min.
2)
A
(min. 20.00 – max. 3000.00)
s
(min.
(non existent, existent)
s
(min.
(1–chanel no sup, 1–chanelWithSup,
2–chanel no Sup, 2–chanelWithSup)
(min.
3)
s
(min.
s
(min.
s
(min.
(single–phase, three–phase)
s
(min.
0.10 – max.
0.80)
0.20 – max.
4.00)
0.00 – max.
0.80)
0.20 – max.
4.00)
0.02 – max.
1.00)
0.00 – max.
1.00)
0.00 – max.
0.80)
0.05 – max.
1.00)
0.05 – max.
1.00)
0.00 – max.
1.00)
0.00 – max.
1.00)